Fluke 1736 and 1738 Three-Phase Power Quality Loggers
Specifications: Fluke 1736 and 1738 Three-Phase Power Quality Loggers
Specifications | |||||
Accuracy | |||||
Parameter | Range | Resolution | Intrinsic Accuracy at Reference Conditions (% of Reading +% of Full Scale) | ||
Voltage | 1000 V | 0.1 V | ±(0.2% + 0.01%) | ||
Current: Direct input | i17xx-flex 1500 12" | 150 A | 0.1 A | ±(1% + 0.02%) | |
1500 A | 1 A | ±(1% + 0.02%) | |||
i17xx-flex 3000 24" | 300 A | 1 A | ±(1% + 0.03%) | ||
3000 A | 10 A | ±(1% + 0.03%) | |||
i17xx-flex 6000 36" | 600 A | 1 A | ±(1.5% + 0.03%) | ||
6000 A | 10 A | ±(1.5% + 0.03%) | |||
i40s-EL clamp | 4 A | 1 mA | ±(0.7% + 0.02%) | ||
40 A | 10 mA | ±(0.7% + 0.02%) | |||
Frequency | 42.5 Hz to 69 Hz | 0.01 Hz | ±(0.1%) | ||
Auxillary input | ±10 V dc | 0.1 mV | ±(0.2% + 0.02%) | ||
Voltage min/max | 1000 V | 0.1 V | ±(1% + 0.1%) | ||
Current min/max | Defined by accessory | Defined by accessory | ±(5% + 0.2%) | ||
THD on voltage | 1000% | 0.1% | ±0.5 | ||
THD on current | 1000% | 0.1% | ±0.5 | ||
Voltage harmonics 2nd to 50th | 1000 V | 0.1 V | ≥ 10 V: ±5% of reading | ||
< 10 V: ±0.5V | |||||
Current harmonics 2nd to 50th | Defined by accessory | Defined by accessory | ≥ 3% of current range: ±5% of reading | ||
< 3% of current range: ±0.15% of range | |||||
Unbalance | 100% | 0.1% | ±0.2 | ||
Intrinsic Uncertainty ±(% of reading +% of range)¹ | |||||
Parameter | Influence quantity | iFlex1500-12 | iFlex3000-24 | iFlex6000-36 | i40S-EL |
150 A / 1500 A | 300 A / 3000 A | 600 A / 6000 A | 4 A / 40 A | ||
Active Power P | PF ≥ 0.99 | 1.2% + 0.005% | 1.2% + 0.0075% | 1.7% + 0.0075% | 1.2% + 0.005% |
Active Energy Ea | PF ≥ 0.99 | 1.2% + 0.005% | 1.2% + 0.0075% | 1.7% + 0.0075% | 1.2% + 0.005% |
Apparent power S | 0 ≤ PF ≤ 1 | 1.2% + 0.005% | 1.2% + 0.0075% | 1.7% + 0.0075% | 1.2% + 0.005% |
Apparent Energy Eap | 0 ≤ PF ≤ 1 | 1.2% + 0.005% | 1.2% + 0.0075% | 1.7% + 0.0075% | 1.2% + 0.005% |
Reactive power Q | 0 ≤ PF ≤ 1 | 2.5% of measured apparent power | |||
Reactive Energy Er | 0 ≤ PF ≤ 1 | 2.5% of measured apparent power | |||
Power Factor PF | - | ±0.025 | |||
Displacement Power Factor | - | ±0.025 | |||
DBF/cosϕ | - | ±0.025 | |||
Additional uncertainty in% of range¹ | VP-N>250 V | 0.015% | 0.0225% | 0.0225% | 0.015% |
¹Range = 1000 V x Irange
|
Electrical Specifications | |||||||
Power Supply | |||||||
Voltage range | 100 V to 500 V using safety plug input when powering from the measurement circuit | ||||||
100 V to 240 V using standard power cord (IEC 60320 C7) | |||||||
Power consumption | Maximum 50 VA (max. 15 VA when powered using IEC 60320 input) | ||||||
Efficiency | ≥ 68.2% (in accordance with energy efficiency regulations) | ||||||
Maximum no-load consumption | < 0.3 W only when powered using IEC 60320 input | ||||||
Mains power frequency | 50/60 Hz ±15% | ||||||
Battery | Li-ion 3.7 V, 9.25 Wh, customer-replaceable | ||||||
On-battery runtime | Four hours in standard operating mode, up to 5.5 hours in power saving mode | ||||||
Charging time | < 6 hours | ||||||
Data Acquisition | |||||||
Resolution | 16-bit synchronous sampling | ||||||
Sampling frequency | 10.24 kHz at 50/60 Hz, synchronized to mains frequency | ||||||
Input signal frequency | 50/60 Hz (42.5 to 69 Hz) | ||||||
Circuit types | 1-φ, 1-φ IT, Split phase, 3-φ delta, 3-φ wye, 3-φ wye IT, 3-φ wye balanced, 3-φ Aron/Blondel (2-element delta), 3-φ delta open leg, Currents only (load studies) | ||||||
Data storage | Internal flash memory (not user replaceable) | ||||||
Memory size | Typical 10 logging sessions of 8 weeks with 1-minute intervals and 500 events¹ | ||||||
¹The number of possible logging sessions and logging period depends on user requirements. | |||||||
Basic Interval | |||||||
Measured parameters | Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy | ||||||
Averaging interval | User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min | ||||||
Averaging time min/max values | Voltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30 Aux, Power: 200ms | ||||||
Demand Interval (Energy Meter Mode) | |||||||
Measured parameters | Energy (Wh, varh, VAh), PF, maximum demand, cost of energy | ||||||
Interval | User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off | ||||||
Power Quality Measurements | |||||||
Measured parameter | Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD | ||||||
Averaging interval | 10 min | ||||||
Individual harmonics | 2nd to 50th harmonic | ||||||
Total harmonic distortion | Calculated on 50 harmonics | ||||||
Events | Voltage: dips, swells, interruptions, current: inrush current | ||||||
Triggered recordings | Full cycle RMS updated every half cycle of voltage and current (Urms1/2 according to IEC61000-4-30) | ||||||
Waveform of voltage and current (1738) | |||||||
Standards Compliance | |||||||
Harmonics | IEC 61000-4-7: Class 1 | ||||||
IEEE 519 (short time harmonics) | |||||||
Power quality | IEC 61000-4-30 Class S, IEC62586-1 (PQI-S device) | ||||||
Power | IEEE 1459 | ||||||
Power quality compliance | EN50160 (for measured parameters) | ||||||
Interfaces | |||||||
USB-A | File transfer via USB flash drive, firmware updates Max. current: 120 mA | ||||||
WiFi | File transfer and remote control via direct connection or WiFi infrastructure | ||||||
Bluetooth | Read auxiliary measurement data from Fluke Connect® 3000 series modules (requires 1738 or 1736 upgrade option) | ||||||
USB-mini | Data download device to PC | ||||||
Voltage Inputs | |||||||
Number of inputs | 4 (3 phases and neutral) | ||||||
Maximum input voltage | 1000 Vrms, CF 1.7 | ||||||
Input impedance | 10 MΩ | ||||||
Bandwidth (-3 dB) | 42.5 Hz - 3.5 kHz | ||||||
Scaling | 1:1 and variable | ||||||
Measurement category | 1000 V CAT III/600 V CAT IV | ||||||
Current Inputs | |||||||
Number of inputs | 4, mode selected automatically for attached sensor | ||||||
Input voltage | Clamp input: 500 mVrms/50 mVrms; CF 2.8 | ||||||
Rogowski coil input | 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4; all at nominal probe range | ||||||
Range | 1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 12" | ||||||
3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 24" | |||||||
6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 36" | |||||||
40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL | |||||||
Bandwidth (-3 dB) | 42.5 Hz - 3.5 kHz | ||||||
Scaling | 1:1 and variable | ||||||
Auxiliary Inputs | |||||||
Number of inputs | 2 | ||||||
Input range | 0 to ±10 V dc, 1reading/s | ||||||
Scale factor | Format: mx + b (gain and offset) user configurable | ||||||
Displayed units | User configurable (7 characters, for example, °C, psi, or m/s) | ||||||
Wireless Connection | |||||||
Number of inputs | 2 | ||||||
Supported modules | Fluke Connect® 3000 series | ||||||
Acquisition | 1 reading/s | ||||||
Environmental Specifications | |||||||
Operating temperature | -10 °C to +50 °C (14 °F to 122 °F) | ||||||
Storage temperature | -20 °C to +60 °C (-4 °F to 140 °F), with battery: -20 °C to +50 °C (-4 °F to 122 °F) | ||||||
Operating humidity | 10 °C to 30 °C (50 °F to 86 °F) max. 95% RH | ||||||
30 °C to 40 °C (86 °F to 104 °F) max. 75% RH | |||||||
40 °C to 50 °C (104 °F to 122 °F) max. 45% RH | |||||||
Operating altitude | 2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV) | ||||||
Storage altitude | 12,000m | ||||||
Enclosure | IP50 in accordance with EN60529 | ||||||
Vibration | MIL-T-28800E, Type 3, Class III, Style B | ||||||
Safety | IEC 61010-1 | ||||||
IEC Mains Input: Overvoltage Category II, Pollution Degree 2 | |||||||
Voltage Terminals: Overvoltage Category IV, Pollution Degree 2 | |||||||
IEC 61010-2-031: CAT IV 600 V / CAT III 1000 V | |||||||
Electromagnetic compatibility | EN 61326-1: Industrial CISPR 11: Group 1, Class A | ||||||
Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment) | |||||||
USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103 | |||||||
Temperature coefficient | 0.1 x accuracy specification/°C | ||||||