  • Fluke 1760 Three-Phase Energy Logger

Fluke 1760 Three-Phase Energy Logger

Specifications: Fluke 1760 Three-Phase Energy Logger

Overview of Measurement Functions
Statistical evaluationPower quality statistics according to EN50160 and DISDIP tables like ITIC, CEBEMA, ANSI
Event listDips, swells and interruptions are detected and stored in the event list. Also any trigger which fires generates an event added to this list.
The Event list shows the exact time when the event occurred as well as the duration and magnitude. Sorting by several attributes of these events is possible to select one for further root cause analysis.
RMS values, transients and fast transients can be stored if a trigger fires
Continuous recordingFluke 1760 records rms values together with corresponding minimum and maximum values for:
• Voltage
• Current
• Power P, Q, S
• Power Factor
• kWh
• Flicker
• Unbalance
• Frequency
• Harmonics/Interharmonics continuously with the following time aggregations: Day, 10 min, Free Interval, e.g.: 15 min, 2 h
Triggered recordingsrmsAggregation time is adjustable between 10 ms (1/2 cycle), 20 ms (1 cycle), 200 ms (10/12 cycles) or 3 sec (150/180 cycles).
Calculating rms values, Harmonics and Interharmonics is performed synchronous to the power frequency.
Basic aggregation for harmonics and interharmonics is 200 ms
Sample rate is 10.24 kHz for all 8 channels
Mains signallingPhases and N-conductor, Voltage and current
Online modeVariable refresh rate. This feature allows verification of instrument set up and delivers a quick overview of oscilloscope, transients and events.
General Data
Intrinsic uncertaintyrefers to reference conditions and is guaranteed for two years
Quality systemdeveloped, manufactured as per ISO 9001: 2000
Environment conditionsOperating temp. range0°C to +50°C; 32°F to +122°F
Working temp. range-20°C to +50°C; -4°F to +122°F
Storage temp. range20°C to +60°C; -4°F to 140°F
Reference temperature23°C ±2 K; 74°F ±2 K
Climatic classB2 (IEC 654-1), -20°C to +50°C; -4°F to +122°F
Max. operating altitude2000 m: max. 600 V CAT IV1
power supply: 300 V CAT III 5000 m: max 600 V CAT III1
power supply: 300 V CAT II
1. Depending on sensor
Reference conditionsEnvironment temperature23°C ±2 K ; 74°F ±2 K
Power supply230 V ±10%
Power frequency50 Hz / 60 Hz
Signaldeclared input voltage Udin
Averaging10 minute intervals
HousingInsulated, robust plastics housing
EMCEmissionClass-A as per IEC/EN 61326-1
ImmunityIEC/EN 61326-1
Power supplyRangeAC: 83 V to 264 V, 45 to 65 Hz
DC: 100 V to 375 V
SafetyIEC/EN 61010-1 2nd edition
300 V CAT III
Power consumptionNIMH, 7.2 V, 2.7 Ah
Battery packIn case of a power supply failure an internal battery maintains the supply for up to 40 minutes. Afterwards, or in case of discharged accumulators the Fluke 1760 is turned off and continues the measurements with the latest settings as soon as the supply voltage returns. The battery can be replaced by the user.
DisplayFluke 1760 features LED indicators for the status of the 8 channels, phase sequence, power supply (mains or accumulator), memory usage, time synchronization, and data transfer.
Power LEDPermanent light: normal power supply from mains.
OFF: supply via internal accumulator in case of a power failure.
Channel LEDs 3-color LEDs per channel forOverload condition
Under load condition
Data memory2 GB Flash memory
Memory modelLinear
InterfacesEthernet (100 MB/s), compatible to Windows® XP, 7 and 8, RS 232, external modem via RS 232
Baud rate for RS 2329600 Baud to 115 kBaud
Dimensions (H x W x D)325 x 300 x 65 mm; 2.8 x 11.8 x 2.6 in
Weightappr. 4.9 kg; 10.8 lbs (without accessories)
Warranty2 years
Calibration interval1 year recommended for Class-A, otherwise 2 years
Signal Conditioning
Range for 50 Hz systems50 Hz ±15% (42.5 Hz to 57.5 Hz)
Range for 60 Hz systems60 Hz ±15% (51 Hz to 69 Hz)
Resolution16 ppm
Sampling frequency for 50 Hz power frequency10.24 kHz, The sampling rate is synchronized to mains frequency.
Uncertainty for frequency measurements< 20 ppm
Uncertainty of internal clock< 1 s / day
Measurement intervalsAggregation of the interval values as per IEC 61000-4-30 Class-A
Min-, Max-valuesHalf cycle, e.g.: 10 ms rms values at 50Hz
TransientsSample rate 100 kHz to 10 MHz per channel
Harmonicsas per IEC 61000-4-7:2002: 200 ms
Flickeras per EN 61000-4-15:2003: 10 min (Pst), 2 h (Plt)
Measurement Inputs
Number of inputs8 galvanically isolated inputs for voltage and current measurements.
Sensor safetyup to 600 V CAT IV depending on sensor
Basic safety300 V CAT III
Nominal voltage (rms)100 mV
Range (peak value)280 mV
Overload capacity (rms)1000 V, continuously
Voltage rise ratemax. 15 kV / µs
Input resistance1 MΩ
Input capacitance5 pF
Input filterEach channel is equipped with a passive low-pass filter, an anti-aliasing filter and a 16-bit A/D converter. All channels are sampled synchronously with a common quartz-controlled clock pulse.
The filters protect against voltage transients and limit the signal rise rate, reduce high frequency components and especially the noise voltage above half the sampling rate of the A/D converter by 80 dB, thus achieving very small measuring errors in an exceptionally large amplitude range. This is also valid under extreme operating conditions like transient voltages at the output of converters.
Uncertainties
Uncertainty at reference conditionsUncertainty including the voltage sensors is in compliance with IEC 61000-4-30 Class-A. All voltage sensors are suitable for DC up to 5 kHz
With Sensor 1000 V0,1% at Udin = 480 V and 600 V P-N
Sensor 600 V0,1% at Udin = 230 V P-N
Intrinsic uncertainty for harmonicsClass I as per EN 61000-4-7:2002
Reference conditions23°C ±2 K < 60% rH; 74°F ±2 K < 60% rH
Warmed up instrument > 3h
Power supply: 100 V to 250 V AC
Temperature drift100 ppm / K
Aging< 0.05% / year
Common mode rejection> 100 dB at 50 Hz
Temperature driftChange of amplification through temperature: < 0.005%/K
AgingChange of amplification due to ageing: < 0.04%/year
NoiseNoise voltage, input short-circuited: < 40 µV
DC±(0.2% rdg + 0.1% sensor)

Write a review

Note: HTML is not translated!
   Bad           Good

Fluke 1760 Three-Phase Energy Logger

  • Product Code:Fluke 1760 Three-Phase Energy Logger
  • Availability:In Stock

Tags: FLUKE

K & P Intertrade Co., Ltd. - Certify

กรมพัฒนาธุรกิจการค้า Trustmarkthai

สินค้าของเรา

เครื่องกำเนิดไฟฟ้า · รอกยกของ · ไม้ชักฟิวส์ · ไม้ฉนวน · บันไดสไลด์ · มีดปอกสาย · ชุดประกอบฉนวนค้ำยันสายไฟ · Ratchet Hoist แบบผ้าใบ · Ratchet Cable Cutter · Insulator Cover · InsulatedHanger · Conductor Cutter with Insulated Handles · Conductor Cover 46 kv · Clamp stick grip all type ขนาด 8 ฟุต · Clamp Stick grip all type ขนาด 12 ฟุต · สว่านไร้สาย · ล้อวัดระยะทาง · ประแจบล๊อคไฟฟ้าไร้สาย (BRUSHLESS CORDLESS IMPACT WRENCH) · เทปวัดระยะชนิดโลหะ · ตู้แผงสวิตช์ · ตู้เก็บเครื่องมือ · เครื่องอัดลมใช้มอเตอร์ไฟฟ้า · เครื่องมือบีบหลอดต่อสายไฮดรอลิค · เครื่องมือบีบคอนเนคเตอร์ แบบ H · เครื่องมือต่อสายลงดิน (Grounding Equipment) · เครื่องมือจับและดึงสาย (Wire Grip Come Along) Overall outside · เครื่องดึงสาย (Coffing Hoist) · อุปกรณ์ระบบไฟฟ้า · สวิตซ์ตัดตอนแรงสูง · หางปลา · หลอดต่อสาย · สลักเข้าปลายสาย · พีจีคอนเนคเตอร์ · ฉนวนป้องกันไฟฟ้าลัดวงจร · ฉนวนครอบล่อฟ้า · เครื่องมือช่างไฟฟ้าอุตสาหกรรม · เครื่องมือไฮดรอลิก · เครื่องมือแบตเตอรี่ไร้สายดิสคอนเนคติ้งสวิตซ์แบริเออร์ · ฉนวนครอบบุชชิ่ง · ตาข่าย · แผ่นอลูมิเนียม · ฉนวนครอบดรอปเอาท์ฟิวส์ · หนามป้องกันสัตว์ · อุปกรณ์ระบบไฟฟ้า · หม้อแปรงไฟฟ้า · ROADMAPTOSTRONGGRIDLV · แคล้มป์สติ๊ก · ClampStick · เชือกใยยักษ์ · เชือก Handline · KNIPEX · เครื่องตรวจจับแรงดันไฟฟ้า · UNI · สายกันตก · UNI9103 · เข็มขัดปีนเสา · YQK · SME · ขายดี · หมวกปีกรอบ · หมวกนิรภัย S-Guard · MSA V-Gard full brim · คีมตัดสาย · คัทเตอร์ตัดสาย · CableCutter · คีมตัดลวดเหล็ก · คัทเตอร์เฟืองทด · คัทเตอร์ตัดสายเคเบิ้ล · คีมย้ำ · คีมบีบ · แคล้มป์สติ๊ก · KANDP · Milwaukee · CHANCE · RITZ · KUDOS · ZUPPER  · FLUKE · Klauke Hydraulic Crimp Tool · Google · 




Official Facebook Page

เนื้อหาส่วนนี้อาจไม่แสดงกรณีใช้ผ่านมือถือบางรุ่น ทางบริษัทฯ ขออภัยในความไม่สะดวก

4 TOP Facebook Official Page Post

เนื้อหาส่วนนี้อาจไม่แสดงกรณีใช้ผ่านมือถือบางรุ่น ทางบริษัทฯ ขออภัยในความไม่สะดวก


Chinese (Simplified)Chinese (Traditional)EnglishFrenchIndonesianJapaneseKoreanRussianThaiKhmerLao