Fluke 1770 Series Three-Phase Power Quality Analyzers
Product overview: Fluke 1770 Series Three-Phase Power Quality Analyzers
Automatic measurements. More flexibility. Better power quality troubleshooting.
Fluke 1770 Series Three-Phase Power Quality Analyzers eliminate the complexities of power quality logging, troubleshooting, and analysis. Engineered to be the faster, easier way to perform power quality studies, the 1770 Series offers automatic measurements, a straightforward user interface and setup, best-in-class specifications, and a simplified reporting platform. The instrument can also be powered directly from the measurement circuit, eliminating the need to find a power outlet or use a lengthy extension cord
With the 1770 Series you’ll never miss a critical power quality event—from fast transients up to 8 kV, harmonics up to 30 kHz, dips and swells, as well as the voltage, current, and power measurements that enable you to characterize your electrical system.
Fluke 1770 Series Three-Phase Power Quality Analyzers eliminate the complexities of power quality logging, troubleshooting, and analysis. Engineered to be the faster, easier way to perform power quality studies, the 1770 Series offers automatic measurements, a straightforward user interface and setup, best-in-class specifications, and a simplified reporting platform. The instrument can also be powered directly from the measurement circuit, eliminating the need to find a power outlet or use a lengthy extension cord
With the 1770 Series you’ll never miss a critical power quality event—from fast transients up to 8 kV, harmonics up to 30 kHz, dips and swells, as well as the voltage, current, and power measurements that enable you to characterize your electrical system.
Automatic measurement capture
Whether you’re performing a quick system check or a detailed power quality study, consistent data is key. The Fluke 1770 Series offers a unique automatic measurement capture system that helps ensure you’re collecting the right data every time, while still giving you the flexibility to select and adjust specific parameters as needed. More than 500 power quality parameters are captured by default and the guided setup makes it easy to select the right parameters for the system you’re working on. Logged data is instantly viewable, downloadable, and shareable with Fluke Energy Analyze Plus software so you never need to wait to finish a session before reviewing results or analyzing data.


Whether you’re performing a quick system check or a detailed power quality study, consistent data is key. The Fluke 1770 Series offers a unique automatic measurement capture system that helps ensure you’re collecting the right data every time, while still giving you the flexibility to select and adjust specific parameters as needed. More than 500 power quality parameters are captured by default and the guided setup makes it easy to select the right parameters for the system you’re working on. Logged data is instantly viewable, downloadable, and shareable with Fluke Energy Analyze Plus software so you never need to wait to finish a session before reviewing results or analyzing data.


Ultimate measurement confidence
The Fluke 1770 Series are 2-in-1 devices that combine the troubleshooting functionality of a power quality meter with the robust analysis and logging capabilities of a standalone power quality analyzer—in a single, easy-to-use, handheld device.
The ‘PQ Meter’ function gives you immediate access to live onscreen data in the field so you can quickly identify potential problems while troubleshooting. The detailed ‘PQ Logging and Analysis’ function eliminates the complexity of performing power quality studies by guiding you through the setup process ensuring you’re capturing the right data every time. Couple these measurement modes with a unique measurement connection autocorrect function and you can be confident that you never need to worry about going back for a second measurement—even if you were unsure about what to look for when you started.
The Fluke 1770 Series are 2-in-1 devices that combine the troubleshooting functionality of a power quality meter with the robust analysis and logging capabilities of a standalone power quality analyzer—in a single, easy-to-use, handheld device.
The ‘PQ Meter’ function gives you immediate access to live onscreen data in the field so you can quickly identify potential problems while troubleshooting. The detailed ‘PQ Logging and Analysis’ function eliminates the complexity of performing power quality studies by guiding you through the setup process ensuring you’re capturing the right data every time. Couple these measurement modes with a unique measurement connection autocorrect function and you can be confident that you never need to worry about going back for a second measurement—even if you were unsure about what to look for when you started.
Powerful analysis software with easy-to-create reports
Fluke 1770 Series Power Quality Analyzers come standard with the powerful Fluke Energy Analyze Plus software, designed to eliminate the hassles found with other multi-purpose application software. Energy Analyze Plus helps you evaluate power quality data right out of the box and without extensive training.
Energy Analyze Plus makes downloading, analyzing, tracking, and reporting power quality and energy data easier than ever. Quickly compare results to historical values, benchmark against industry norms, compare measured data to local conditions, and create a more complete picture of what’s occurring across your facility, even as the data is still being collected. Energy Analyze Plus offers unified support for the Fluke 1730, 1740, and 1770 Series of Energy Loggers and Power Quality Analyzers.
- “In-workshop” and “in-the-field” setup and download through PC application software
- Simple data downloads using USB memory stick, WiFi, LTE, wired Ethernet, or USB cable
- Analyze every measured detail of energy consumption and power quality state-of-health with automated reporting
- One-touch reporting creates standardized reports conforming to standards like EN 50160, IEEE 519, GOST 33073 IEC 61000-2-2, or export data in PQDIF or NeQual compatible format or CSV for use with third-party software
- Advanced analysis allows the user to choose any available logged parameter and create a highly customized view of measurements for advanced data correlation


Fluke 1770 Series Power Quality Analyzers come standard with the powerful Fluke Energy Analyze Plus software, designed to eliminate the hassles found with other multi-purpose application software. Energy Analyze Plus helps you evaluate power quality data right out of the box and without extensive training.
Energy Analyze Plus makes downloading, analyzing, tracking, and reporting power quality and energy data easier than ever. Quickly compare results to historical values, benchmark against industry norms, compare measured data to local conditions, and create a more complete picture of what’s occurring across your facility, even as the data is still being collected. Energy Analyze Plus offers unified support for the Fluke 1730, 1740, and 1770 Series of Energy Loggers and Power Quality Analyzers.
- “In-workshop” and “in-the-field” setup and download through PC application software
- Simple data downloads using USB memory stick, WiFi, LTE, wired Ethernet, or USB cable
- Analyze every measured detail of energy consumption and power quality state-of-health with automated reporting
- One-touch reporting creates standardized reports conforming to standards like EN 50160, IEEE 519, GOST 33073 IEC 61000-2-2, or export data in PQDIF or NeQual compatible format or CSV for use with third-party software
- Advanced analysis allows the user to choose any available logged parameter and create a highly customized view of measurements for advanced data correlation


High-speed voltage transient capture
Transients negatively impact otherwise healthy systems every day and their potential to damage your equipment can’t be underestimated. Whether your system is experiencing impulsive or oscillatory transients, the results can be devastating and cause problems ranging from insulation failures to total equipment failures. The Fluke 1775 and Fluke 1777 incorporate advanced transient capture technology to help you clearly identify high-speed voltage transients, so you have the data you need to stop them in their tracks. The Fluke 1775 Power Quality Analyzer has 1MHz sampling capability to capture fast transients, while the Fluke 1777 Power Quality Analyzer has 20MHz sampling capability to capture the fastest transients in high detail.
Transients negatively impact otherwise healthy systems every day and their potential to damage your equipment can’t be underestimated. Whether your system is experiencing impulsive or oscillatory transients, the results can be devastating and cause problems ranging from insulation failures to total equipment failures. The Fluke 1775 and Fluke 1777 incorporate advanced transient capture technology to help you clearly identify high-speed voltage transients, so you have the data you need to stop them in their tracks. The Fluke 1775 Power Quality Analyzer has 1MHz sampling capability to capture fast transients, while the Fluke 1777 Power Quality Analyzer has 20MHz sampling capability to capture the fastest transients in high detail.
From traditional industrial systems to renewable energy systems to electric vehicles, we’ve got you covered
The Fluke 1770 Series was designed to be safe and easy to use in any measurement environ¬ment. The 1770 Series allows you to capture a full range of power quality variables as well as high-speed waveforms, high-speed transients, and higher frequency harmonics, all of which are instantly viewable on the large, high-resolution screen. With a best-in-class CAT IV 600 V / CAT III 1000 V overvoltage rating, these analyzers can be used at the service entrance or downstream, measuring AC and DC inputs, and harmonics measuring up to 30 kHz. With the 1770 Series you can be confident that you’ll capture the data you need to make better maintenance decisions no matter the task.
Applications 1773 1775 1777 Energy surveys and load testing ✔ ✔ ✔ Harmonic surveys ✔ ✔ ✔ Nuisance circuit breaker tripping ✔ ✔ Electric utility power quality surveys ✔ ✔ Discovery of equipment failures caused by 8kV microsecond transients ✔ ✔ Discovery of equipment failures caused by 8kV nanosecond transients ✔

The Fluke 1770 Series was designed to be safe and easy to use in any measurement environ¬ment. The 1770 Series allows you to capture a full range of power quality variables as well as high-speed waveforms, high-speed transients, and higher frequency harmonics, all of which are instantly viewable on the large, high-resolution screen. With a best-in-class CAT IV 600 V / CAT III 1000 V overvoltage rating, these analyzers can be used at the service entrance or downstream, measuring AC and DC inputs, and harmonics measuring up to 30 kHz. With the 1770 Series you can be confident that you’ll capture the data you need to make better maintenance decisions no matter the task.
Applications | 1773 | 1775 | 1777 |
---|---|---|---|
Energy surveys and load testing | ✔ | ✔ | ✔ |
Harmonic surveys | ✔ | ✔ | ✔ |
Nuisance circuit breaker tripping | ✔ | ✔ | |
Electric utility power quality surveys | ✔ | ✔ | |
Discovery of equipment failures caused by 8kV microsecond transients | ✔ | ✔ | |
Discovery of equipment failures caused by 8kV nanosecond transients | ✔ |

Compliant to international standards
The Fluke 1770 Series offers the best-in-class accuracy you’ve come to expect from a Fluke Power Quality Analyzer in a future IEC 61000-4-30 Class A edition 3 compliant package. On top of that, the 1770 Series has been engineered to meet the future requirements of Class A edition, for conformance to EN 50160 and IEEE 519, so you’ll be prepared to tackle tomorrow’s measurement requirements, today.

The Fluke 1770 Series offers the best-in-class accuracy you’ve come to expect from a Fluke Power Quality Analyzer in a future IEC 61000-4-30 Class A edition 3 compliant package. On top of that, the 1770 Series has been engineered to meet the future requirements of Class A edition, for conformance to EN 50160 and IEEE 519, so you’ll be prepared to tackle tomorrow’s measurement requirements, today.

Work where, when, and how you want
No two days in the field are the same. You need a power quality analyzer that can go where you go and do what you need it to when you get there. With a full range of accessories and built-in features the Fluke 1770 Series makes it easier to get your job done. The slim ergonomic design and integrated hand strap make it easy to hold and the included hanging kit makes it easy to secure your analyzer inside a cabinet. The integrated internal power supply allows the unit to be powered directly from the measured circuit, while a 90-minute battery helps ensure you can still access and review data even when you aren’t connected to a live system.
Quickly and easily transfer data to your PC using the USB C, USB A, Ethernet, Wi-Fi, cellular network support options, depending on your requirements. With an internal GPS module and an optional double insulated antenna extension cable, for amplifying GPS signals indoors, you can easily time sync your data for more accurate troubleshooting and analysis.
No two days in the field are the same. You need a power quality analyzer that can go where you go and do what you need it to when you get there. With a full range of accessories and built-in features the Fluke 1770 Series makes it easier to get your job done. The slim ergonomic design and integrated hand strap make it easy to hold and the included hanging kit makes it easy to secure your analyzer inside a cabinet. The integrated internal power supply allows the unit to be powered directly from the measured circuit, while a 90-minute battery helps ensure you can still access and review data even when you aren’t connected to a live system.
Quickly and easily transfer data to your PC using the USB C, USB A, Ethernet, Wi-Fi, cellular network support options, depending on your requirements. With an internal GPS module and an optional double insulated antenna extension cable, for amplifying GPS signals indoors, you can easily time sync your data for more accurate troubleshooting and analysis.
Calculate current harmonics limits
When downloading data from the Fluke 1770 Series Power Quality Analyzers the included Energy Analyze Plus software package can compare measured voltage and current harmonic statistical data to different standards, like EN 50160 or IEEE 519, to determine if they exceed compliance limits. This powerful predictive maintenance feature enables current harmonics to be observed before distortion appears in the voltage allowing you to prevent unexpected failures or non-compliance situations and increase system uptime. With the proliferation of inverter-based loads and power generation, keeping current harmonics in check is becoming increasingly critical to ensure reliable power quality and avoid system downtime.


When downloading data from the Fluke 1770 Series Power Quality Analyzers the included Energy Analyze Plus software package can compare measured voltage and current harmonic statistical data to different standards, like EN 50160 or IEEE 519, to determine if they exceed compliance limits. This powerful predictive maintenance feature enables current harmonics to be observed before distortion appears in the voltage allowing you to prevent unexpected failures or non-compliance situations and increase system uptime. With the proliferation of inverter-based loads and power generation, keeping current harmonics in check is becoming increasingly critical to ensure reliable power quality and avoid system downtime.


Calculate money lost to energy waste in terms of real dollars with the Energy Loss Calculator
The Energy Loss Calculator (ELC) mode in the Fluke 1770 Series Power Quality Analyzers is designed to discover where energy losses exist in your electrical system using Fluke’s patented Unified Power calculation developed by the University of Valencia. In every electrical system, some energy is wasted and that energy is not delivered to the loads in your system to drive them. This waste comes from:
- Transmission of effective power – Heat generated as power flows through cables
- Reactive power – Does not drive the load but consumes energy
- Unbalance losses – Unbalanced loads contribute to wasted energy
- Distortion power – Non-linear loads create harmonics that consume power, but do not perform work
- Neutral losses – Neutral losses can be due to both unbalance and harmonics, leading to increased heat and requiring larger conductors
The Energy Loss Calculator (ELC) mode in the Fluke 1770 Series Power Quality Analyzers is designed to discover where energy losses exist in your electrical system using Fluke’s patented Unified Power calculation developed by the University of Valencia. In every electrical system, some energy is wasted and that energy is not delivered to the loads in your system to drive them. This waste comes from:
- Transmission of effective power – Heat generated as power flows through cables
- Reactive power – Does not drive the load but consumes energy
- Unbalance losses – Unbalanced loads contribute to wasted energy
- Distortion power – Non-linear loads create harmonics that consume power, but do not perform work
- Neutral losses – Neutral losses can be due to both unbalance and harmonics, leading to increased heat and requiring larger conductors
What's in the box:
Fluke 1777
- 3PHVL-17XX flat cable voltage test lead 3-phase+N
- AC285 black alligator clips (set of four)
- AC285 green alligator clip
- MP1-3R/1B Magnetic Probes (set of four)*
- Black 1M USB-C cable
- Line cords (US, EU, UK, AUS, BRA)
- FLUKE-17XX-TL blue stacking 0.18M test lead
- Green test lead
- WI-FI/BLE MODULE **
- 17XX CABLE MARKER cable marker set
- 17XX BATT W/HOUSING battery (installed)
- MA-C8 wall outlet adapter
- I17XX-FLEX1500/18 flexible 1500A AC current clamps (set of four)
- 32GB micro-SD card (installed) *
- C1777 Hard case *
* Items not included with 1775 and 1773 standard models
** Items not included with 1773 standard model
Fluke 1777
- 3PHVL-17XX flat cable voltage test lead 3-phase+N
- AC285 black alligator clips (set of four)
- AC285 green alligator clip
- MP1-3R/1B Magnetic Probes (set of four)*
- Black 1M USB-C cable
- Line cords (US, EU, UK, AUS, BRA)
- FLUKE-17XX-TL blue stacking 0.18M test lead
- Green test lead
- WI-FI/BLE MODULE **
- 17XX CABLE MARKER cable marker set
- 17XX BATT W/HOUSING battery (installed)
- MA-C8 wall outlet adapter
- I17XX-FLEX1500/18 flexible 1500A AC current clamps (set of four)
- 32GB micro-SD card (installed) *
- C1777 Hard case *
* Items not included with 1775 and 1773 standard models
** Items not included with 1773 standard model
Specifications: Fluke 1770 Series Three-Phase Power Quality Analyzers
Key features
Voltage inputs Number of inputs 4 inputs, 3 phases and neutral referenced to PE (5 connectors) Measurement category 1000 V CAT III / 600 V CAT IV Maximum input voltage 1000 V rms / 1000 V dc (1700 Vpk) Nominal voltage range Wye and single phase: variable (50 V – 1000 V)
Delta: Variable (100 V – 1000 V)
IEC 61000-4-30 Class A compliance for the nominal voltages (Vdin) 100 V – 690 V Input impedance 10 MΩ between P-P and P-N, 5 MΩ between P-PE and N-PE Bandwidth DC to 30 kHz for PQ measurements, excluding transients Resolution 24-bit synchronous sampling Sampling frequency 80 kS/s at 50/60 Hz Scaling 1:1, variable for use of potential transformers
Voltage transients Measurement range ±8 kV Sampling rate 1775: 1 MS/s
1777: 1 MS/s, 20 MS/s Bandwidth DC to 1 MHz Trigger Adjustable trigger level. Triggers on high-frequency components > 1.5 kHz Resolution 14-bit synchronous sampling
Current inputs Number of inputs 4 inputs 3 phases and Neutral, range selected automatically to attached sensor Range AC 1 A to 1500 A with i17XX-FLEX1500 12
1 A to 1500 A with i17XX-FLEX1500 18
1 A to 1500 A with i17XX-FLEX1500 24
3 A to 3000 A with i17XX-FLEX3000 24
6 A to 6000 A with i17XX-FLEX6000 36
40 mA to 40 A with clamp i40s-EL
4 A to 400 A with clamp i400s-EL DC 20 A to 2000 A with 80i-2010-EL clamp Bandwidth DC to 30 kHz Resolution 24-bit synchronous sampling Sampling frequency 80 kS/s at 50/60 Hz Scaling 1:1, variable Input voltage Clamp: 50 mV / 500 mV rms; CF 2.8
Rogowski Coil: 15 mV / 150 mV rms at 50 Hz, 18 mV / 180 mV rms at 60 Hz; CF 4
all at nominal probe range Input impedance 11 kΩ
Aux inputs Wired connection with 17XX-AUX adapter Number of inputs 2 Input range Direct: 0 V dc to ± 10 V dc
0 V to 1000 V dc Input impedance Direct: 2.92 MΩ Scale factor Format: mx + b (gain and offset) user configurable Displayed units User configurable (up to 8 characters, for example °C, psi, or m/s)
Data acquisition voltage and current Input mains frequency DC, 50/60 Hz 15 % (42.5 Hz … 57.5 Hz, 51 Hz … 69 Hz) Topologies 1-φ, 1-φ IT, Split phase, 3-φ delta, 3-φ wye IT, 3-φ Aron/Blondel (2 element delta), 3-φ delta open leg, 3-φ high leg delta Data storage Fluke 1773/1775: 8 GB internal (expandable with microSD card)
Fluke 1777: 32 GB microSD card (installed) Memory size Typical 10 logging sessions of 8 weeks with 1-minute intervals and 100 events.
The number of possible logging sessions and logging period depends on user requirements Real time accuracy Internal: 3 ppm (0.26 s per day, 8 s per month)
NTP (internet time): Depending on internet latency, typical < 0.1 s absolute to UTC
GPS: < 1 ms absolute to UTC
Trend interval Measured parameter See operator manual Trend interval User selectable: 1 sec, 3 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min Averaging interval min/max values Voltage, Current: ½ cycle RMS (20 ms at 50 Hz, 16.7 ms at 60 Hz)
Aux, Power: 200 ms Total harmonic distortion THD for voltage and current is calculated on 50 harmonics
Power quality measurements Measured parameter See operator manual Harmonics h0 … h50
% fund and RMS for voltage, current and power
Phase angles for voltage and current up to h11 Interharmonics ih0… ih50
% fund and RMS for voltage and current Supraharmonics 2–9 kHz with 200 Hz bins
9–30 khz with 2 kHz bins
RMS for voltage and current Harmonics measurement method Grouped, sub-grouped and single harmonic bins according to IEC 61000-4-7.
Method selected automatically based on configured PQ standard or user configurable. Total harmonic distortion Calculated on up to 50 harmonics (depends on selected PQ standard)
Fluke 1770 Series Three-Phase Power Quality Analyzers
- Product Code:Fluke 1770 Series Three-Phase Power Quality Analyzers
- Availability:In Stock
Tags: FLUKE

สินค้าของเรา
เครื่องกำเนิดไฟฟ้า ·
รอกยกของ · ไม้ชักฟิวส์ · ไม้ฉนวน · บันไดสไลด์ · มีดปอกสาย
· ชุดประกอบฉนวนค้ำยันสายไฟ · Ratchet Hoist แบบผ้าใบ · Ratchet Cable Cutter · Insulator Cover · InsulatedHanger
· Conductor Cutter with Insulated Handles · Conductor Cover 46 kv · Clamp stick grip
all type ขนาด 8 ฟุต · Clamp Stick
grip all type ขนาด 12 ฟุต · สว่านไร้สาย · ล้อวัดระยะทาง · ประแจบล๊อคไฟฟ้าไร้สาย (BRUSHLESS CORDLESS IMPACT WRENCH) · เทปวัดระยะชนิดโลหะ · ตู้แผงสวิตช์ · ตู้เก็บเครื่องมือ · เครื่องอัดลมใช้มอเตอร์ไฟฟ้า ·
เครื่องมือบีบหลอดต่อสายไฮดรอลิค · เครื่องมือบีบคอนเนคเตอร์
แบบ H · เครื่องมือต่อสายลงดิน (Grounding Equipment)
· เครื่องมือจับและดึงสาย (Wire Grip Come Along) Overall
outside · เครื่องดึงสาย (Coffing Hoist) · อุปกรณ์ระบบไฟฟ้า
· สวิตซ์ตัดตอนแรงสูง · หางปลา · หลอดต่อสาย · สลักเข้าปลายสาย · พีจีคอนเนคเตอร์ · ฉนวนป้องกันไฟฟ้าลัดวงจร ·
ฉนวนครอบล่อฟ้า · เครื่องมือช่างไฟฟ้าอุตสาหกรรม · เครื่องมือไฮดรอลิก · เครื่องมือแบตเตอรี่ไร้สายดิสคอนเนคติ้งสวิตซ์แบริเออร์
· ฉนวนครอบบุชชิ่ง · ตาข่าย · แผ่นอลูมิเนียม · ฉนวนครอบดรอปเอาท์ฟิวส์ · หนามป้องกันสัตว์ · อุปกรณ์ระบบไฟฟ้า · หม้อแปรงไฟฟ้า · ROADMAPTOSTRONGGRIDLV · แคล้มป์สติ๊ก
· ClampStick · เชือกใยยักษ์ · เชือก Handline
· KNIPEX · เครื่องตรวจจับแรงดันไฟฟ้า · UNI · สายกันตก · UNI9103 · เข็มขัดปีนเสา · YQK ·
SME · ขายดี · หมวกปีกรอบ · หมวกนิรภัย S-Guard · MSA V-Gard full brim · คีมตัดสาย · คัทเตอร์ตัดสาย · CableCutter · คีมตัดลวดเหล็ก ·
คัทเตอร์เฟืองทด · คัทเตอร์ตัดสายเคเบิ้ล ·
คีมย้ำ · คีมบีบ · แคล้มป์สติ๊ก
·
KANDP · Milwaukee · CHANCE · RITZ · KUDOS · ZUPPER · FLUKE · Klauke Hydraulic Crimp Tool · Google ·
Official Facebook Page
เนื้อหาส่วนนี้อาจไม่แสดงกรณีใช้ผ่านมือถือบางรุ่น ทางบริษัทฯ ขออภัยในความไม่สะดวก
4 TOP Facebook Official Page Post
เนื้อหาส่วนนี้อาจไม่แสดงกรณีใช้ผ่านมือถือบางรุ่น ทางบริษัทฯ ขออภัยในความไม่สะดวก
Voltage inputs | |
---|---|
Number of inputs | 4 inputs, 3 phases and neutral referenced to PE (5 connectors) |
Measurement category | 1000 V CAT III / 600 V CAT IV |
Maximum input voltage | 1000 V rms / 1000 V dc (1700 Vpk) |
Nominal voltage range | Wye and single phase: variable (50 V – 1000 V) Delta: Variable (100 V – 1000 V) IEC 61000-4-30 Class A compliance for the nominal voltages (Vdin) 100 V – 690 V |
Input impedance | 10 MΩ between P-P and P-N, 5 MΩ between P-PE and N-PE |
Bandwidth | DC to 30 kHz for PQ measurements, excluding transients |
Resolution | 24-bit synchronous sampling |
Sampling frequency | 80 kS/s at 50/60 Hz |
Scaling | 1:1, variable for use of potential transformers |
Voltage transients | |
---|---|
Measurement range | ±8 kV |
Sampling rate | 1775: 1 MS/s 1777: 1 MS/s, 20 MS/s |
Bandwidth | DC to 1 MHz |
Trigger | Adjustable trigger level. Triggers on high-frequency components > 1.5 kHz |
Resolution | 14-bit synchronous sampling |
Current inputs | ||
---|---|---|
Number of inputs | 4 inputs 3 phases and Neutral, range selected automatically to attached sensor | |
Range | AC | 1 A to 1500 A with i17XX-FLEX1500 12 1 A to 1500 A with i17XX-FLEX1500 18 1 A to 1500 A with i17XX-FLEX1500 24 3 A to 3000 A with i17XX-FLEX3000 24 6 A to 6000 A with i17XX-FLEX6000 36 40 mA to 40 A with clamp i40s-EL 4 A to 400 A with clamp i400s-EL |
DC | 20 A to 2000 A with 80i-2010-EL clamp | |
Bandwidth | DC to 30 kHz | |
Resolution | 24-bit synchronous sampling | |
Sampling frequency | 80 kS/s at 50/60 Hz | |
Scaling | 1:1, variable | |
Input voltage | Clamp: 50 mV / 500 mV rms; CF 2.8 Rogowski Coil: 15 mV / 150 mV rms at 50 Hz, 18 mV / 180 mV rms at 60 Hz; CF 4 all at nominal probe range | |
Input impedance | 11 kΩ |
Aux inputs | |
---|---|
Wired connection with 17XX-AUX adapter | |
Number of inputs | 2 |
Input range | Direct: 0 V dc to ± 10 V dc 0 V to 1000 V dc |
Input impedance | Direct: 2.92 MΩ |
Scale factor | Format: mx + b (gain and offset) user configurable |
Displayed units | User configurable (up to 8 characters, for example °C, psi, or m/s) |
Data acquisition voltage and current | |
---|---|
Input mains frequency | DC, 50/60 Hz 15 % (42.5 Hz … 57.5 Hz, 51 Hz … 69 Hz) |
Topologies | 1-φ, 1-φ IT, Split phase, 3-φ delta, 3-φ wye IT, 3-φ Aron/Blondel (2 element delta), 3-φ delta open leg, 3-φ high leg delta |
Data storage | Fluke 1773/1775: 8 GB internal (expandable with microSD card) Fluke 1777: 32 GB microSD card (installed) |
Memory size | Typical 10 logging sessions of 8 weeks with 1-minute intervals and 100 events. The number of possible logging sessions and logging period depends on user requirements |
Real time accuracy | Internal: 3 ppm (0.26 s per day, 8 s per month) NTP (internet time): Depending on internet latency, typical < 0.1 s absolute to UTC GPS: < 1 ms absolute to UTC |
Trend interval | |
---|---|
Measured parameter | See operator manual |
Trend interval | User selectable: 1 sec, 3 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min |
Averaging interval min/max values | Voltage, Current: ½ cycle RMS (20 ms at 50 Hz, 16.7 ms at 60 Hz) Aux, Power: 200 ms |
Total harmonic distortion | THD for voltage and current is calculated on 50 harmonics |
Power quality measurements | |||||||||
---|---|---|---|---|---|---|---|---|---|
Measured parameter | See operator manual | ||||||||
Harmonics | h0 … h50 % fund and RMS for voltage, current and power Phase angles for voltage and current up to h11 | ||||||||
Interharmonics | ih0… ih50 % fund and RMS for voltage and current | ||||||||
Supraharmonics | 2–9 kHz with 200 Hz bins 9–30 khz with 2 kHz bins RMS for voltage and current | ||||||||
Harmonics measurement method | Grouped, sub-grouped and single harmonic bins according to IEC 61000-4-7. Method selected automatically based on configured PQ standard or user configurable. | ||||||||
Total harmonic distortion | Calculated on up to 50 harmonics (depends on selected PQ standard) | ||||||||
Fluke 1770 Series Three-Phase Power Quality Analyzers
Tags: FLUKE สินค้าของเราเครื่องกำเนิดไฟฟ้า ·
รอกยกของ · ไม้ชักฟิวส์ · ไม้ฉนวน · บันไดสไลด์ · มีดปอกสาย
· ชุดประกอบฉนวนค้ำยันสายไฟ · Ratchet Hoist แบบผ้าใบ · Ratchet Cable Cutter · Insulator Cover · InsulatedHanger
· Conductor Cutter with Insulated Handles · Conductor Cover 46 kv · Clamp stick grip
all type ขนาด 8 ฟุต · Clamp Stick
grip all type ขนาด 12 ฟุต · สว่านไร้สาย · ล้อวัดระยะทาง · ประแจบล๊อคไฟฟ้าไร้สาย (BRUSHLESS CORDLESS IMPACT WRENCH) · เทปวัดระยะชนิดโลหะ · ตู้แผงสวิตช์ · ตู้เก็บเครื่องมือ · เครื่องอัดลมใช้มอเตอร์ไฟฟ้า ·
เครื่องมือบีบหลอดต่อสายไฮดรอลิค · เครื่องมือบีบคอนเนคเตอร์
แบบ H · เครื่องมือต่อสายลงดิน (Grounding Equipment)
· เครื่องมือจับและดึงสาย (Wire Grip Come Along) Overall
outside · เครื่องดึงสาย (Coffing Hoist) · อุปกรณ์ระบบไฟฟ้า
· สวิตซ์ตัดตอนแรงสูง · หางปลา · หลอดต่อสาย · สลักเข้าปลายสาย · พีจีคอนเนคเตอร์ · ฉนวนป้องกันไฟฟ้าลัดวงจร ·
ฉนวนครอบล่อฟ้า · เครื่องมือช่างไฟฟ้าอุตสาหกรรม · เครื่องมือไฮดรอลิก · เครื่องมือแบตเตอรี่ไร้สายดิสคอนเนคติ้งสวิตซ์แบริเออร์
· ฉนวนครอบบุชชิ่ง · ตาข่าย · แผ่นอลูมิเนียม · ฉนวนครอบดรอปเอาท์ฟิวส์ · หนามป้องกันสัตว์ · อุปกรณ์ระบบไฟฟ้า · หม้อแปรงไฟฟ้า · ROADMAPTOSTRONGGRIDLV · แคล้มป์สติ๊ก
· ClampStick · เชือกใยยักษ์ · เชือก Handline
· KNIPEX · เครื่องตรวจจับแรงดันไฟฟ้า · UNI · สายกันตก · UNI9103 · เข็มขัดปีนเสา · YQK ·
SME · ขายดี · หมวกปีกรอบ · หมวกนิรภัย S-Guard · MSA V-Gard full brim · คีมตัดสาย · คัทเตอร์ตัดสาย · CableCutter · คีมตัดลวดเหล็ก ·